TY - JOUR
T1 - Parametric Study to Repair Leaks in Water Pipe Using the Low-Pressure Cold Spray Technique
AU - Meng, Yuxian
AU - Saito, Hiroki
AU - Bernard, Chrystelle A.
AU - Ichikawa, Yuji
AU - Ogawa, Kazuhiro
N1 - Funding Information:
The authors would also like to acknowledge the Institute of Fluid Science at Tohoku University, which supported this research through grant J21Ly17 under the label of the Collaborative Research Project, and Université de Lyon.
Funding Information:
The authors are grateful to Tohoku University and Fukushima Daiichi D&D Engineering Company, TEPCO Holdings, Inc. for funding the joint research project "Research and Development for Decommissioning Fukushima Daiichi Nuclear Power Plants."
Publisher Copyright:
© 2022, ASM International.
PY - 2022/12
Y1 - 2022/12
N2 - Water leakage due to corrosion damage is a significant issue in thermal and nuclear power plants. This study proposes to use a low-pressure cold spray (LPCS) method to repair efficiently active leaks in pipes. A mixture of Sn/Zn powder was cold sprayed over a 0.5 mm diameter active leaking hole using the LPCS method at various parameters, viz., powder mixing ratio, gas temperature, and gas pressure. The results demonstrated that the hole could be plugged within 10 s by the rigid layer of coating formed by the LPCS method, even though the active water continued to flow through the pipe. Based on the results, the effect of the powder mixing ratio, gas temperature, and gas pressure on the coating hardness, components, and thickness have been studied in detail. Furthermore, the particle velocity/temperature was calculated by computational fluid dynamics simulations to clarify the particle impact behavior. Moreover, the microstructure of the coating-substrate interface was observed using scanning electron microscopy, and the bonding mechanism of the mixed powder has been discussed.
AB - Water leakage due to corrosion damage is a significant issue in thermal and nuclear power plants. This study proposes to use a low-pressure cold spray (LPCS) method to repair efficiently active leaks in pipes. A mixture of Sn/Zn powder was cold sprayed over a 0.5 mm diameter active leaking hole using the LPCS method at various parameters, viz., powder mixing ratio, gas temperature, and gas pressure. The results demonstrated that the hole could be plugged within 10 s by the rigid layer of coating formed by the LPCS method, even though the active water continued to flow through the pipe. Based on the results, the effect of the powder mixing ratio, gas temperature, and gas pressure on the coating hardness, components, and thickness have been studied in detail. Furthermore, the particle velocity/temperature was calculated by computational fluid dynamics simulations to clarify the particle impact behavior. Moreover, the microstructure of the coating-substrate interface was observed using scanning electron microscopy, and the bonding mechanism of the mixed powder has been discussed.
KW - active leak repair
KW - bonding mechanism
KW - cold spray
KW - Sn/Zn mixed powder
UR - http://www.scopus.com/inward/record.url?scp=85139140201&partnerID=8YFLogxK
UR - http://www.scopus.com/inward/citedby.url?scp=85139140201&partnerID=8YFLogxK
U2 - 10.1007/s11666-022-01469-y
DO - 10.1007/s11666-022-01469-y
M3 - Article
AN - SCOPUS:85139140201
SN - 1059-9630
VL - 31
SP - 2560
EP - 2576
JO - Journal of Thermal Spray Technology
JF - Journal of Thermal Spray Technology
IS - 8
ER -